PLANET Industrial 4-Port RS232/422/485 Modbus Gateway

PLANET Industrial 4-Port RS232/422/485 Modbus Gateway
PLANET Industrial 4-Port RS232/422/485 Modbus Gateway
  • ΔΙΑΘΕΣΙΜΟΤΗΤΑ: 15-20 Ημέρες
  • Κωδικός Προϊόντος: IMG-2400T
  • EAN: 4711605285155
2icon RS-232
6icon RS485 RS422
7icon Modbus-TCP
0icon Modbus-RTU-ASCII
8icon -40-degree-~75-degree
3icon Redundant Power
8icon di do


Economical Solution for Industrial Modbus TCP/RTU/ASCII Network Integration

PLANET has added the Industrial Modbus TCP/IP Protocol to its easily-integrated industrial management level products that come with SCADA/HMI system and other data acquisition systems on factory floors. Moreover, the industrial IT SNMP network is upgraded to the industrial automation Modbus TCP/IP network. PLANET industrial management level products with the Modbus TCP/IP Protocol offer flexible network connectivity solutions for the industrial automation environment.

To complete the industrial automation environment application solution, PLANET has announced a first industrial level 4-port RS232/422/485 Modbus Gateway, IMG-2400T, a bridge that converts between Modbus TCP/IP Protocol and Modbus RTU/ASCII Protocol. It features a wide operating temperature range from -40 to 75 degrees C and a compact but rugged IP40 metal housing.

A Conversion Bridge for Flexible Network Deployment

The IMG-2400T can be a conversion bridge between the equipment with the Modbus RTU/ASCII Protocol and the administrator workstations that run the Modbus TCP/IP Protocol. The RS232/422/485 serial interface of the IMG-2400T provides the Modbus RTU/ASCII operation mode and various baud rate options to meet the demand of integration between the Modbus TCP/IP Protocol, Modbus RTU Master/Slave Protocol and Modbus ASCII Master/Slave Protocol.

The advantage of having the IMG-2400T is to assist users to build an industrial environment between the Modbus TCP/IP Protocol and the Modbus RTU/ASCII Protocol easily, thus offering an application solution to the industrial control equipment without Ethernet ports and the industrial control equipment can only control through an industrial PC workstation or industrial control panel. 

In addition, the effective integration solution of Modbus Ethernet devices, Modbus serial equipment or multi Modbus master / slave in an industrial hybrid network brings the following:

  • Master mode supports up to 32 TCP slave connection requests
  • Slave mode supports up to 32 TCP master connections

 

Remote Management 

The IMG-2400T makes the connected industrial Modbus RTU/ASCII equipment become IP-based facilities and is able to connect to the Modbus TCP/IP network via its RS232/422/485 serial interface and 10/100BASE-TX RJ45 Ethernet port. It provides a remote web management and telnet interface for efficient remote network management.  The IMG-2400T also provides PLANET Modbus Gateway utility tool and supports PLANET Smart Discovery utility to help network administrator to easily get the current IP subnet address information or change the IP subnet address setting of the IMG-2400T.

Modbus Serial Port State Monitoring

The IMG-2400T shows the details of the total bytes transmitted and received on the RS232/422/485 serial interface, and the detailed total number of frames transmitted and received on the remote web/telnet management interface. This function allows network administrator to check the status and statistics of the IMG-2400T via the single RS232/422/485 serial interface.

 

Stable Performance in Hardened Environment Design

The IMG-2400T provides a high level of immunity against electromagnetic interference and heavy electrical surges which are usually found on plant floors or in curb-side traffic control cabinets. Its operating temperature ranging from -40 to 75 degrees C allows the IMG-2400T to be placed in almost any difficult environment. 

The IMG-2400T is equipped with a compact IP40-rated metal case that allows wall mounting for efficient use of cabinet space. The IMG-2400T also provides an integrated power supply source with wide-ranging voltages (12 to 48V DC) ideally suitable for worldwide operation with high availability applications.

 

Effective Alarm Alert for Better Protection

The IMG-2400T comes with a Fault Alarm feature which can alert the users when there is something wrong with the Serial Device Server. With this ideal feature, the users would not have to waste time finding where the problem is. It will help to save time and human resource. The IMG-2400T provides event alert function to help to diagnose the abnormal device owing to whether or not there is a break of the network connection, or the rebooting response.

Dual Power Input for High Availability Network System

The IMG-2400T features a strong dual power input system with wide-ranging voltages (12V~48V DC) incorporated into customer’s automation network to enhance system reliability and uptime. In the example below, when Power Supply 1 fails to work, the hardware failover function will be activated automatically to keep powering the IMG-2400T via Power Supply 2 without any break of operation.

Digital Input and Digital Output for External Alarm

With digital input and digital output on its front panel, an external alarm can help users via the digital input to detect and log external device status (such as door intrusion detector), and then immediately send an event alarm to the administrator. The digital output can be used to alarm the administrator if the IMG-2400T serial port shows DCD, changed DSR or power failure.

Serial Interface
Serial Ports 4 x DB9 male
Serial Standards RS232 / 4-wire RS422 or RS485 / 2-wire RS485
Baud Rate (Data Rate) 50bps to 921Kbps
Data Bits 5, 6, 7, 8
Parity Type 1, 1.5, 2
Stop Bit Odd, Even, None, Space, Mark
Flow Control RTS/CTS and DTR/DSR (RS232 only) XON/XOFF
Signals RS232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND RS422: Tx+, Tx-, Rx+, Rx-, GND 4-wire RS485: Tx+, Tx-, Rx+, Rx-, GND 2-wire RS485: Data A (+), Data B (-), GND
Pin Assignment
PinRS232RS422
RS485-4W
RS485-2W
1DCDTxD+--
2RxDTxD---
3TxDRxD-Data-
4DTRRxD+Data+
5GNDGNDGND
6DSR----
7RTS----
8CTS----
9------
Operation Mode RTU Master/RTU Slave/ASCII Master/ASCII Slave Master mode: Supports up to 32 TCP slave connection requests Slave mode: Supports up to 32 TCP master connection requests
Serial Line Protection 2KV isolation protection 1KV (level 2) surge protection 15KV ESD protection
Ethernet Interface
Ethernet Ports 2 x RJ45
Standard 10/100BASE-TX
Distance 100m
Switch Architecture Store-and-Forward
Address Table 1K
ESD Protection 6KV
Surge Protection 2KV
Hardware
Installation DIN-rail kit and wall-mount ear
Enclosure IP 40 metal
Dimensions (W x D x H) 50 x 87 x 135 mm
Weight 625g
LED Indicators System: Power 1, Power 2, Fault, SYS,I/O TP Port: Link/ Active Serial Port: Tx and Rx
Power Requirements 12~48V DC, redundant power with reverse polarity protection
Power Consumption Full Loading 12VDC: 0.419A (5.1 watts) 24VDC: 0.227A (5.4 watts) 48VDC: 0.136A (6.5 watts)
Connector Removable 6-pin terminal block for power input Pin 1/2 for Power 1, Pin 3/4 for fault alarm, Pin 5/6 for Power 2
DI and DO 2 Digital Input (DI): Level 0: -24V~2.1V (±0.1V) Level 1: 2.1V~24V (±0.1V) Input Load to 24V DC, 10mA max.2 Digital Output (DO): Open collector to 24V DC, 100mA max.
Alarm Provides one relay output for power failure Alarm relay current carry ability: 1A @ DC 24V
Reset Button < 5 sec: System reboot > 5 sec: Factory default
Management
Management Interfaces Web management Telnet Console management Windows-based VCOM Utility management SNMPv1, v2c / SNMP Trap UNI-NMS monitoring PLANET Smart Discovery Utility
IP Version IPv4 and IPv6
Operation Mode RTU Master RTU Slave ASCII Master ASCII Slave
Virtual COM Utility Platform Supports Windows-based only:  Windows XP  Windows Server 2003  Windows 7  Windows Server 2008  Windows 8 (Must install the latest version of WinPcap)  Windows Server 2012 (Must install the latest version of WinPcap)  Windows 10
Fault Alarm Record: System log / SNMP trap
Time NTP
Security Allow max. 4 accessible IP address hosts/ranges
SNMP MIBs RFC1213 MIB-II RFC1317 RS232-like MIB
Standards Conformances
Regulatory Compliance FCC Part 15 Class A, CE Certification Class A
Stability Testing IEC60068-2-32 (Free fall) IEC60068-2-27 (Shock) IEC60068-2-6 (Vibration)
Standards IEEE 802.3 10BASE-T IEEE 802.3u 100BASE-TX RFC 768 UDP RFC 793 TFTP RFC 791 IP RFC 792 ICMP RFC 854 Telnet RFC 958 NTP RFC 1591 DNS (client only) RFC 1908 SNMPv2c RFC 2068 HTTP RFC 2131 DHCP Client RFC 2732 Format for Literal IPv6 Addresses in URL's RFC 3315 DHCPv6 Client RFC 3513 IPv6 Addressing Architecture RFC 3596 DNSv6 RFC 4443 ICMPv6 EIA/TIA RS232/422/485
Regulatory Approval RoHS
Environment
Operating Temperature -40 ~ 75 degrees C
Storage Temperature -40 ~ 85 degrees C
Humidity 5 ~ 95% (non-condensing)